K-FACTOR TRANSFORMER

Today’s modern electronic, electric components and circuitry utilize switching mode power supplies for their operation which are non-linear loads in nature and unlike a linear load which uses current from the power source continuously over the sinusoidal cycle where else a non-linear load draws current in pulses from the power source thereby creating harmonic distortion. These harmonics currents cause significant power system problems such as; circuit breakers and fuses blowing far below current ratings, Neutrals in transformers and panel boards are much hotter than their ratings, transformer overheating even when operating well within their specified nameplate rating

A K-factor rated transformer is designed not to mitigate harmonics but to handle a degree of harmonic load currents without overheating. The K-rating number of the transformer are values used to determine how much harmonic current a transformer can handle without exceeding its maximum temperature rise level. K-factor values range from K1, K4, K9, K13, K20 up to K50. For a K-factor of K1 transformer is used for linear loads only. The calculation of K-factor for a given load is outlined in IEEE C57.110.

k factor tx

TECHNICAL SPECIFICATIONS

CAPACITY

  • Up to 2500kVA

RATED FREQUENCY

  • 50Hertz
  • 60Hertz

INSULATION CLASSIFICATION

  • Class F & H
  • Others upon request

REFERRENCE STANDARD

  • IEC 60076
  • IEC 61558

TRANSFORMER CORE MATERIAL

  • High grade electrical steel

WINDING CONDUCTORS

  • Copper or Aluminium wire
  • Copper or Aluminium foils

OPTIONAL ACCESSORIES

  • Enclosures up to IP54
  • MCCB with or without shunt trip
  • Ammeter and Voltmeter
  • Temperature controller
  • Fan fail alarm
  • BMS open relay contacts

TECHNICAL SPECIFICATIONS

RATED VOLTAGE

  • Up to 1000V

AMBIENT TEMPERATURE

  • 40oC
  • Others upon request